basicDIM Wireless passive MP

Tridonic  ·  Gateways  ·  DALI-2 Components

basicDIM Wireless passive MP

Casambi Ready module that doubles as a DALI gateway

A Casambi Ready module that sits inside the luminaire or enclosure and puts a DALI line onto the Casambi mesh — no separate gateway box, no control cabling back to a panel. It is passive: it draws its own power from the DALI bus rather than needing a supply of its own, so a single IEC 62386 power supply feeds both the drivers and the module. Devices form a network of up to 250 nodes automatically, and each one can also work as a repeater to extend coverage.

  • Works as a DALI gateway — bridges a DALI line onto the Casambi mesh
  • Passive: powered from the DALI bus, no separate supply needed
  • No external gateway box, no control wiring to a panel
  • Self-forming mesh of up to 250 nodes (Evolution networks)
  • Bluetooth 4.0 / 5.0 Low Energy, up to 150 m range
  • Supports Tridonic PSensor and DALI MSensor for daylight and presence
  • Doubles as a repeater to extend wireless coverage
  • Firmware updatable over the air; 5 year Tridonic guarantee
Manufacturer datasheet
PDF · 584 KB

Technical specification

Article no.28005689
ProductbasicDIM Wireless passive MP
TypeCasambi Ready wireless module / DALI gateway
Supply voltage9.5 – 22.5 V, from an IEC 62386 compatible power supply
Current draw13 mA (30 mA at start)
Power consumption0.16 W typical, at 16 V
InterfaceDigital interface to IEC 62386
AddressesUp to 4 single or group addresses (A0–A3 / G0–G3); remaining drivers via broadcast
Radio protocolBluetooth 4.0 or 5.0 Low Energy
Frequency2.4 – 2.483 GHz
Output power< +20 dBm E.I.R.P.
Radio rangeUp to 150 m, line of sight, mounted above 4 m
Mesh networkUp to 250 nodes — Standard and Long Range networks
SensorsTridonic PSensor, DALI MSensor, DALI XC G3 push-button interface
Status LEDOrange steady in operation; green flashes on Identify
Connection cable350 mm rigid, 0.5 mm²
Dimensions L × W × H78.6 × 53.3 × 27.3 mm
HousingPA polyamide, white
ProtectionIP20, IK03
Ambient temperatureta −40 … +70 °C · tc 72 °C
Storage temperaturets −40 … +75 °C
Humidity0 – 90 %
LifetimeUp to 100,000 h at tc = 72 °C
Guarantee5 years (Tridonic manufacturer conditions)
Security updates5 years from date of purchase
StandardsEN 55015, EN 61347-1, EN 61347-2-11, EN 61547, EN 62479, EN 62493, ETSI EN 300 328, ETSI EN 301 489-1, ETSI EN 301 489-17
Packaging18 pcs per carton · 0.03 kg each

Specifying it as a gateway: the module addresses up to four DALI single or group addresses individually (A0–A3 / G0–G3), depending on the device profile selected in the app. Any further drivers on the same line respond to broadcast. If a project needs more than four independently controlled groups behind one module, split the line or use a second module.

Specification taken from the manufacturer datasheet and subject to change without notice. Confirm against the current datasheet before ordering.