FRANKCAS Sentry Spot recessed non-maintained emergency spot

FRANKCAS  ·  Emergency Lighting

Sentry Spot

Recessed non-maintained emergency spot — 42 mm cut-out, 3 hour duration

A flush recessed emergency spot that installs through a 42 mm hole, with a hinged low-profile driver that feeds up into a fixed ceiling void. It gives 240 lm open area or 198 lm with the corridor lens, held at constant output for the full rated duration so the spacing you design to is the spacing you still have at hour three. Available in DALI-2 self-test or Casambi wireless.

Specified with FRANKCAS X3. Both control versions are built for automatic testing: the DALI-2 version reports to X3 Direct over the emergency DALI line, and the Casambi version joins the wireless mesh. X3 then runs the EN 62034 calendar, logs every result to the BS 5266-1 logbook and emails you when a fitting fails. See the X3 controller.
  • 42 mm lamp mounting hole — suits fixed ceilings
  • Hinged, low-profile driver for tight ceiling voids
  • 9.3 m spacing open area, 19 m with the corridor lens, from 2.5 m
  • Constant 1.5 W output maintains spacing for the full duration
  • Hidden push-to-test bezel and built-in charge indicator LED
  • Deep discharge protection, constant current / constant voltage charger
  • Pre-wired with 180 mm interconnecting cable
FRANKCAS datasheet
PDF · 214 KB

Ordering information

Part numberControl  ·  description
FC-EL-SP-D2DALI-2 self-test  ·  Open area lamp head, 3 h, DALI-2 / self-test
FC-EL-SP-D2-CLDALI-2 self-test  ·  Corridor lens lamp head, 3 h, DALI-2 / self-test
FC-EL-SP-CWCasambi wireless  ·  Open area lamp head, 3 h, Casambi wireless
FC-EL-SP-CW-CLCasambi wireless  ·  Corridor lens lamp head, 3 h, Casambi wireless

Technical specification

Input supply230 V ±10%, 50/60 Hz
Emergency output240 lm open / 198 lm corridor
Max spacing (2.5 m)9.3 m open / 19 m corridor
Rated duration3 hours
Battery4.4 Ah LiFePO4
Charge time24 hours
Earth leakage< 0.5 mA
Ambient temp.up to +50 °C
IP ratingIP20
Cut-out42 mm
Weight320 g
StandardsEN 60598-1 and EN 60598-2-22 (luminaires for emergency lighting) · EN 50172 / BS 5266-1 (emergency escape lighting systems) · EN 62034 (automatic test systems) · EN 61347-1 and EN 61347-2-7 (emergency driver) · EN 55015, EN 61000-3-2 and EN 61547 (EMC) · EN 62386 and DALI-2 Part 202 for the DALI-2 self-test version · RoHS.

Product standards as applicable to the luminaire and its emergency driver. Declarations of conformity available on request. Specification subject to change without notice. Installation must be carried out by a competent person to BS 7671, with the system designed to BS 5266-1 / EN 50172.

Related products

Start a project

Tell us about the building.
We will specify the system.

Send us a floor plan, a fixture schedule or just a rough idea of the space. We will come back with a controls layout, a product schedule and a commissioning plan.