FRANKCAS Sentry Surface surface non-maintained emergency luminaire

FRANKCAS  ·  Emergency Lighting

Sentry Surface

Surface non-maintained emergency luminaire — round or square, 3 hour duration

A surface-mounted emergency luminaire for ceilings with no void, available as a round or a square cover on a common first-fix gear tray with through-ceiling or side conduit entry. 240 lm open area gives 8 m spacing from a 2.5 m ceiling; the corridor lens takes that to 19 m along an escape route. Available in DALI-2 self-test or Casambi wireless.

Specified with FRANKCAS X3. Both control versions are built for automatic testing: the DALI-2 version reports to X3 Direct over the emergency DALI line, and the Casambi version joins the wireless mesh. X3 then runs the EN 62034 calendar, logs every result to the BS 5266-1 logbook and emails you when a fitting fails. See the X3 controller.
  • Round or square cover on a common gear tray
  • Through-ceiling or side conduit cable entry
  • 8 m spacing open area, 19 m with the corridor lens, from 2.5 m
  • Constant 1.5 W output maintains spacing for the full duration
  • Push-to-test lamp bezel and built-in charge indicator LED
  • 4.4 Ah high-temperature LiFePO4 battery
  • Deep discharge protection; pre-wired for simple installation
FRANKCAS datasheet
PDF · 174 KB

Ordering information

Part numberControl  ·  description
FC-EL-SF-C-D2DALI-2 self-test  ·  Circular cover, open area, 3 h
FC-EL-SF-C-D2-CLDALI-2 self-test  ·  Circular cover, corridor lens, 3 h
FC-EL-SF-S-D2DALI-2 self-test  ·  Square cover, open area, 3 h
FC-EL-SF-S-D2-CLDALI-2 self-test  ·  Square cover, corridor lens, 3 h
FC-EL-SF-C-CWCasambi wireless  ·  Circular cover, open area, 3 h
FC-EL-SF-S-CWCasambi wireless  ·  Square cover, open area, 3 h

Technical specification

Input supply230 V ±10%, 50/60 Hz
Emergency output240 lm open / 198 lm corridor
Max spacing (2.5 m)8 m open / 19 m corridor
Rated duration3 hours
Battery3.2 V 4.4 Ah LiFePO4
Charge time24 hours
Earth leakage< 0.5 mA
Ambient temp.+10 … +35 °C
IP ratingIP20
Diameter178 mm
Weight400 g
StandardsEN 60598-1 and EN 60598-2-22 (luminaires for emergency lighting) · EN 50172 / BS 5266-1 (emergency escape lighting systems) · EN 62034 (automatic test systems) · EN 61347-1 and EN 61347-2-7 (emergency driver) · EN 55015, EN 61000-3-2 and EN 61547 (EMC) · EN 62386 and DALI-2 Part 202 for the DALI-2 self-test version · RoHS.

Product standards as applicable to the luminaire and its emergency driver. Declarations of conformity available on request. Specification subject to change without notice. Installation must be carried out by a competent person to BS 7671, with the system designed to BS 5266-1 / EN 50172.